Hioki Safety Measuring For High-Voltage | DIFFERENTIAL PROBE P9000

Description

DIFFERENTIAL PROBE
P9000

Easily Connect To Hioki Memory HiCorders And HiLoggers For High Voltage Testing

•Compact probe for CAT III 1000V environments

•Use WAVE mode to observe instantaneous waveforms

•Use AC-RMS mode to observe RMS waveforms

•Principal applications…

1. High-voltage battery circuits in vehicles such as EVs and HEVs

2. High-voltage circuits in solar power installations and other alternative energy systems

3. Commercial power circuits, for example 480 Vrms circuits

4. High-voltage surge noise from inverters, motors, and solenoids, etc.

 

Basic Specifications (Accuracy Guaranteed For 1 Year, Post-Adjustment Accuracy Guaranteed For 1 Year)

P9000-01 P9000-02
Measurement functions Waveform monitor output only
Frequency characteristics: DC to 100 kHz, -3 dB
Waveform monitor output/AC RMS value output (switchable)
Wave mode frequency characteristics: DC to 100 kHz, -3 dB
RMS mode frequency characteristics: 30 Hz to 10 kHz; response time: 300 ms (rising) or 500 ms (falling)
Division ratio 1000:1 or 100:1 (user selectable)
DC amplitude accuracy ±0.5% f.s. (f.s. = 1.0 V; voltage division ratio: 1000:1) (f.s. = 3.5 V; voltage division ratio: 100:1)
RMS amplitude accuracy ±1% f.s. (30 Hz to 1 kHz non-inclusive, sine wave), ±3% f.s. (1 kHz to 10 kHz, sine wave)
Input resistance, capacity Between H and L: 10.5 MΩ, 5 pF or less (at 100 kHz)
Max. allowable input 1000 V AC/DC
Max. rated voltage to earth 1000 V AC/DC (CAT III)
Operating temperature -40 ˚C (-40 ˚F) to 80 ˚C (176˚F)
Power supply (1) AC Adapter Z1008 (100 to 240 V AC, 50/60 Hz), 6 VA (including AC adapter) or 0.9 VA (probe only), (2) USB bus power (5 V DC, USB Micro-B receptacle), 0.8 VA, (3) External power supply (2.7 V to 15 V DC)
Dimensions and mass 128 mm (5.04 in)W × 36 mm (1.42 in)H × 22 mm (0.87 in)D, 170 g (6.0 oz), Cord length: Input: 70 cm (2.30 ft) ; output: 1.5 m (4.92 ft)
Accessories Instruction manual ×1, alligator clips ×2, carrying case ×1